Inverter Battery Backup Calculator

Enter the load you want to keep running and your battery's Ah and voltage to get the backup time. Or switch modes and enter the hours you need to see what battery to buy.

What do you want to find?
W
Ah
V
%
%
Backup time –
Energy stored–
Usable–
Reaches your appliances–
Inverter size, at least–

Estimates for a battery in good health at room temperature. Old batteries and heavy loads give less.

A 150 Ah, 12 V inverter battery holds 1,800 watt-hours on paper. Run 300 W of fans and lights from it and simple division says six hours. In practice you get closer to three and a half, and the gap is not a fault in the battery.

Where the missing hours go

Two losses sit between the battery and your fan. First, you shouldn't drain a lead-acid battery flat. Regularly emptying it shortens its life, so inverters cut off well before zero and a sensible plan uses only part of the stored energy. The "usable charge" box is that share, often called depth of discharge. Second, the inverter itself wastes some energy as heat while turning 12 V DC into 230 V AC, which is the efficiency figure.

Backup hours = Ah × battery volts × number of batteries × usable charge × inverter efficiency ÷ load in watts 150 × 12 × 1 × 0.70 × 0.85 ÷ 300 = 3.57 hours (about 3 h 34 min)

The defaults of 70% usable charge and 85% efficiency are middle-of-the-road assumptions, not ratings. Your inverter's manual may give its efficiency, and the battery maker may say how deep it can be discharged. Change both boxes to match.

An evening power cut in a two-bedroom flat

Say you want to keep three ceiling fans, four LED bulbs, the Wi-Fi router and the TV running. With regular 75 W fans that is 351 W, and the single 150 Ah battery above lasts about 3 hours 3 minutes. With 30 W BLDC fans the same set of appliances needs 216 W, and backup stretches to 4 hours 58 minutes. Fans are usually the biggest load on an inverter, so they are where efficiency buys the most time.

How the same battery copes with different loads, at 70% usable charge and 85% efficiency:

LoadBackup from one 150 Ah, 12 V battery
100 W10 h 43 min
200 W5 h 21 min
300 W3 h 34 min
500 W2 h 9 min
750 W1 h 26 min
1,000 W1 h 4 min

Working backwards from the hours you need

Switch the calculator to "Battery needed". For the 351 W flat above and a five-hour cut on a 24 V inverter, the bank has to deliver 351 × 5 ÷ 0.85 = 2,065 Wh, which means buying about 2,950 Wh of battery to stay within 70%. At 24 V that is 123 Ah, so two 150 Ah, 12 V batteries in series cover it, with a little to spare: they give about 6 hours 6 minutes.

On a 12 V inverter, the same flat wanting three hours needs 147 Ah, and one 150 Ah battery just manages it at 3 hours 3 minutes. Two batteries on a 12 V inverter are wired in parallel; on a 24 V inverter they go in series. Either way two identical batteries hold twice the energy, so the backup doubles. The inverter decides the voltage, so check its rating before buying batteries.

Usable charge and battery type

For the 300 W load on one 150 Ah battery, here is what the usable-charge setting does:

SettingBackup at 300 W
50% usable, 85% efficient2 h 33 min
70% usable, 85% efficient3 h 34 min
80% usable, 85% efficient4 h 5 min
90% usable, 90% efficient4 h 52 min

Lithium (LiFePO4) home batteries are usually specified for deeper regular discharge than lead-acid ones, which is why the last row is closer to what a lithium unit of the same Ah can give. Use the figure on your battery's datasheet rather than these examples.

Inverter VA is a different number

The inverter's VA rating limits how many watts it can supply at once; the battery decides for how long. Divide your load by the power factor (0.8 is a common assumption for home loads) to get the minimum VA. The 351 W evening load needs at least 439 VA, so a 600 VA or larger unit leaves room for a fan's start-up. A big battery on an undersized inverter still trips the moment you switch on too much.

Why your real backup may be shorter

Battery capacity is quoted at a slow, steady discharge; the label often says C10 or C20, meaning the Ah figure holds when the battery is drained over 10 or 20 hours. A 300 W load pulls about 29 A from a 12 V battery, which empties a 150 Ah battery much faster than that, and lead-acid batteries deliver fewer Ah when drained quickly. Age, heat and low water levels in flooded batteries cut capacity further. If your backup has been shrinking year by year, the battery is the likely cause, not the inverter.

To build the load figure from your actual appliances, list them in the appliance electricity cost calculator. If power cuts are frequent and the roof gets sun, the solar rooftop calculator covers the cost side of going solar.

Frequently asked questions

Can I add a new battery alongside my old one?

It is best not to. Batteries in the same bank share the load and the charge, and a new battery paired with a tired one, or a 150 Ah with a 100 Ah, ends up overcharged or undercharged. Most installers replace the whole set together.

How long does a flat battery take to recharge?

Roughly the Ah to be put back divided by the charging current, plus extra time because charging is not perfectly efficient and slows down near full. A 150 Ah battery drained to 70% needs about 105 Ah back; at 15 A that is seven hours, and longer once charging losses are counted. The charging current is in the inverter's manual.

Will my inverter run a fridge or a pump?

Running watts are only half the story. Motors and compressors draw several times their running power for a moment when they start, so the inverter's VA rating must cover that surge. Check the appliance and inverter manuals, and expect the fridge to cut backup time sharply because it adds its load to everything else.